ZW7-40.5 Outdoor High-Voltage Vacuum Circuit Breaker

Negotiable
China
Building 2-33, Caicheng Industrial Park, Economic Development Zone, Shangrao City, Jiangxi Province
0793-8876066
Online Contact
Favorite

Product Introduction

Overview

The ZW7-40.5 outdoor high-voltage vacuum circuit breaker is designed for three-phase power systems with AC 50Hz and a voltage of 40.5kV, used for breaking and closing load current, overload current, and short-circuit current.

Main Functions

1. Vacuum arc extinction is adopted, featuring strong breaking capacity, long electrical life, and a mechanical life of 10,000 operations;

2. Simple structure, maintenance-free, and long maintenance-free period;

3. Good insulation performance and strong anti-pollution capability;

4. Can be equipped with spring or electromagnetic operating mechanisms, with reliable mechanical performance and capability for frequent operation; no fire or explosion hazards;

5. Built-in current transformers with measurement accuracy up to Class 0.2, enabling three-phase interactive protection;

6. Equipped with a condensation controller to ensure reliable operation of the circuit breaker under certain temperature and humidity conditions.

Operating Environmental Conditions

1. Ambient air temperature: upper limit +40°C, lower limit -30°C;

2. Altitude: ≤2000m (if a higher altitude is required, the rated insulation level shall be increased accordingly);

3. Wind pressure: not exceeding 700Pa (equivalent to a wind speed of 34m/s);

4. Amplitude: seismic intensity of 8 degrees;

5. Pollution level: Class III;

6. Maximum daily temperature difference: not exceeding 25°C.

Main Technical Parameters

No. Item Unit Parameter
1 Rated voltage kV 40.5
2 Rated insulation level Power frequency withstand voltage Dry kV 95
Wet 80
Lightning impulse withstand voltage (peak) 185
3 Rated current A 1250, 1600, 2000
4 Rated short-circuit breaking current kA 20, 25, 31.5
5 Rated operating sequence Open-0.3s Close Open-180s Close Open
6 Rated short-circuit current breaking operations times (timcs) 12
7 Rated short-circuit making current (peak) kA 50, 63, 80
8 Rated peak withstand current
9 Rated short-time withstand current kA 20, 25, 31.5
10 Rated short-circuit duration current s 4
11 Average opening speed m/s 1.5±0.2
12 Average closing speed 0.7±0.2
13 Contact closing bounce time s ≤3
14 Three-phase closing (opening) simultaneity time difference ≤2
15 Closing time ≤150
16 Opening time ≤60
17 Mechanical life times (timcs) 10000
18 Rated operating voltage and rated voltage of auxiliary circuit V DC220, 110, 24
AC220, 110
19 DC resistance per phase circuit (excluding transformers) μΩ ≤100
20 Allowable wear thickness of moving and static contacts mm 3
21 Weight kg 800