FKN12A-12/FJRB12A-12 Air Compressed Load Switch -- Fuse Combination Apparatus

Negotiable
China
Building 2-33, Caicheng Industrial Park, Economic Development Zone, Shangrao City, Jiangxi Province
0793-8876066
Online Contact
Favorite

Product Introduction

Overview

FKN12-12D/T630-20 type indoor AC high-voltage load switch (hereinafter referred to as FKN12-12D load switch) is a three-phase high-voltage switchgear with a rated voltage of 12kV and a rated frequency of 50Hz. It is used for making and breaking load current, closed-loop current, no-load transformer and cable charging current, and making short-circuit current. The load switch equipped with an earthing switch can withstand short-circuit current.

FKRN12-12D/T125-31.5 type AC high-voltage load switch -- fuse combination apparatus is an indoor high-voltage switchgear that combines the FN12-12D load switch with the S□LAJ-12 (XRNT□-10) high-voltage current-limiting fuse.

It can reliably break any current up to short-circuit current; the load switch breaks the working current, the fuse breaks the short-circuit current, and together they break any overcurrent between the working current and the full short-circuit current. At the same time, the fuse causes the load switch to open through its striker.

Main Applications

FKN12A-12D air-compressed load switch and FKRN12A-12D series air-compressed load switch -- fuse combination apparatus are suitable for 12kV and below three-phase distribution systems, used for the control and protection of power equipment such as transformers, cables, and overhead lines; especially suitable for terminal substations and box-type substations in urban and rural power grids. They are also suitable for the control and protection of ring network and double-radial power supply units.

The FKN12A-12D series air-compressed load switch can make and break load current and overload current.

The FKRN12A-12D series air-compressed load switch -- fuse combination apparatus can make and break load current and overload current, and break line short-circuit current.

Structural Features

1. The load switch, earthing switch, fuse, and mechanism are on one frame, allowing flexible combination, compact structure, small volume, and convenient and simple installation;

2. The break is of straight-moving arrangement, with high dynamic and thermal stability current parameters, and the operation is completed in one action;

3. It has a static contact insulating cover, which structurally isolates the two phases, eliminating the need for inter-phase insulating barriers and break insulating insertion plates, and can prevent arc short-circuit accidents inside the cabinet;

4. It has a unique shutter structure. After the load switch is opened, the shutter automatically isolates the break, providing good protection performance;

5. There are reliable mechanical interlocks between the load switch and the earthing switch and fuse, meeting the "five preventions" requirements;

6. It has two forms: manual operation and electric operation with AC/DC dual-purpose operating power supply, facilitating the realization of the "three remote" requirements of the power system.

Operating Environment Conditions

1. Ambient air temperature: -25℃~+40℃;

2. Altitude not exceeding 1000m;

3. Relative humidity daily average not greater than 95%, monthly average not greater than 90%.

4. Earthquake intensity not exceeding magnitude 8;

5. Locations without fire, explosion hazard, chemical corrosion, or severe vibration;

6. Pollution level: Ⅱ.

Main Technical Parameters

No. Item Unit FKN12A-12D FKRN12A-12D
1 Rated voltage kV 12 12
2 Rated frequency Hz 50 50
3 Rated current A 630 125
4 Rated insulation level 1min
power frequency withstand voltage
To earth, between phases kV 42 42
Isolating break 48 48
Lightning impulse
withstand voltage (peak)
To earth, between phases 75 75
Isolating break 85 85
5 Load switch kA 20 -
Earthing switch 20 20
6 Load switch S 4 -
Earthing switch 2 2
7 Rated short-circuit making current (peak) kA 50 -
8 Rated breaking current Active load breaking current A 630 -
Closed-loop breaking current 630 -
5% active load breaking current 31.5 -
Cable charging current 10 -
Breaking capacity of no-load transformer KVA 1250 1250
9 Rated short-circuit breaking current (current-limiting fuse) kA - 31.5
10 Rated transfer current A - 1200
11 Mechanical life Operations 2000 2000
12 Striker output energy J - 1+0.5
No. Name Unit Data
1 Break gap mm ≥175
2 Center distance between phases 210±2
3 Air gap between phases ≥125
4 Stroke 210±4
5 Over-travel ≥40
6 Three-phase closing asynchronism ms ≤10
7 Three-phase opening asynchronism ≤5
8 Inherent opening time of shunt release 40-65
9 Main circuit resistance μΩ ≤130