Project
|
Description
|
|
Control characteristics
|
Torque compensation
|
Automatic torque compensation function.
|
|
Acceleration and deceleration mode
|
Line, user-defined multi-point curve.
|
|
Automatic voltage adjustment
|
When the grid fluctuates, it can automatically keep the output voltage constant.
|
|
DC braking mode
|
DC braking at startup and DC braking at shutdown.
|
|
Built-in process PID
|
It is convenient to realize the closed-loop control system of process quantity (pressure, temperature, flow, etc.).
|
|
Special features
|
User-programmable application-free function modules:
Logic function module, mathematical function module, timer module, PID module, etc;
Motion control:
Multi-curve acceleration/deceleration function, timer-controlled run/stop control, etc;
Crane function:
Power optimization, crane opening brake function.
|
|
Input/output
terminals
|
Input terminal
|
Rectifier unit configuration 43 D1 interface.
The inverter unit is configured with 8-way D1, 2-way AI and 2-way STO interfaces.
|
|
Shaft out terminal
|
The rectifier unit is configured with 30 DO interfaces.
The inverter unit is configured with 5 DO and 2 AO interfaces.
|
|
Man-machine interface
|
Operation Panel LED
|
Can set the relevant parameters, can also display the output frequency, output voltage, output current and other parameters;
The operation status, fault status and parameter setting status shall have corresponding display contents: function, data and unit.
|
|
Protection function
|
Overcurrent protection, overvoltage protection, undervoltage protection, overheat protection, overload protection, etc.
|
|
Place of use
|
No direct sunlight, no dust and no corrosive environment.
|
|
Environment
|
Altitude
|
Less than 1000 meters, no derating required. For places with an altitude of more than 1000 meters, please reduce the rated voltage and rated output current by 1% for every 100 meters increase. When the altitude exceeds 3000 meters, it is necessary to consult the manufacturer for guidance.
|
|
Ambient temperature
|
-10 ℃ ~ +40 ℃, the ambient temperature exceeds 40 ℃, and derating is required. For every 1 ℃ increase in the ambient temperature, the derating rate is 1%. When the ambient temperature exceeds 50 ℃, consult the manufacturer for guidance. The ambient temperature is lower than -10 ℃, and additional auxiliary heating equipment is required.
|
|
Temperature
|
Less than 95% RH, no water condensation.
|
|
Storage
|
The storage temperature is -20 ℃ ~ +60 ℃. At the same time, due to the characteristics of the electrolytic capacitor, the storage time is more than half a year. The inverter needs to be powered on for 10-30 minutes every six months to charge the electrolytic capacitor.
|
|
Other
|
Efficiency
|
> 98%
|
|
Option Card
|
The inverter unit control board is equipped with 2 slots, which can receive communication card, expansion IO card and PG card.
|
|
Other Interfaces
|
External keyboard interface, CAN communication interface.
|
|
Protection level
|
IP20
|
|
Cooling mode
|
forced air cooling
|
|
Pollution level
|
2
|
|
Noise
|
≤ 80db
|