HF680N Series Multi-Drive VFD

EXW
$290.38-1,452.50 /Set
China
No.6 Ligongyuan Road, WUT National University Science Park, Donghu New Technology Development Zone, Wuhan
027-87923289
Online Contact
Favorite
Product Introduction

Product Overview:
The HF680N series is an air-cooled multi-drive product, including diode rectifier units, regenerative rectifier units, active rectifier units, and inverters, capable of meeting various application requirements. The HF680N four-quadrant multi-drive product consists of a regenerative rectifier unit and inverters, providing a constant DC power supply and perfect energy regeneration for the system, with excellent speed and torque control performance. The regenerative rectifier module and the LCL filter unit together form the regenerative rectifier unit, enabling bidirectional energy flow. It can be used in industries such as ports, tunneling, shipbuilding, metallurgy, cement, petroleum, and mining.

Product Parameters

HF680N01 basic rectification (air cooling) technical parameters

Project

Description

Work

Performance

Input voltage

Three-phase 380V ~ 480V

Three-phase 660V ~ 690V

Rated frequency

50/60Hz

Allowable voltage fluctuation

-15% to + 10%

Allowable frequency fluctuation

The allowable range of frequency variation is fLN ± 2% (± 4% for independent power supply network).

Frequency change rate: ≤ 2% fLN/s.

Operation instruction mode

Digital input, digital output, support Profibus DP, Profinet and other communications.

Efficiency

> 98%

Overload capacity

The overload capacity is 150% of the rated output current, and the overload is allowed for 1 minute every 5 minutes.

DC bus voltage

0 ~ input voltage * 1.414

Protection function

Overcurrent, overvoltage, undervoltage, overtemperature, phase loss, etc.

HF680N02 active rectifier (air-cooled) technical parameters

Project

Description

Power

Input

Input voltage

Three-phase 380V ~ 480V

Three-phase 380V ~ 500V

Three-phase 660V ~ 690V

Rated frequency

50/60Hz

Allowable voltage fluctuation

-15% to + 10%

Control

Characteristics

Control mode

AFE control

Operation instruction mode

Digital input, digital output.

Input power factor

0.999 (at the rated current of the rectifier feedback product)

Current harmonic content

Less than 3% (at the rated current of the rectified feedback product).

Overload capacity

Light overload condition: 150 of the output current, allowing 1 minute of overload every 5 minutes;

Heavy overload condition: 180% of the output current, 1 minute of overload is allowed every 5 minutes.

DC bus voltage

570V ~ 710V (three-phase 400V incoming line, adjustable according to incoming line voltage).

570V ~ 810V (three-phase 500V incoming line, adjustable according to incoming line voltage).

1000V ~ 1150V (three-phase 690V incoming line, adjustable according to incoming line voltage).

Carrier Frequency

1kHz to 10kHz

HF680N03 inverter (air-cooled) technical parameters

Project

Description

Power

Input

Input power

540V ~ 700V, DC power supply

540V ~ 810V, DC power supply

800V ~ 1150V, DC power supply

Control

Characteristics

Control mode

Closed-loop vector control (VC), open-loop vector control (SVC), V/F control.

Operation instruction mode

Digital input, digital output, relay output, support Profibus DP and other communications.

Maximum output voltage

380V ~ 460V (corresponding to the input voltage).

380V ~ 500V (corresponding to the input voltage).

660V ~ 690V (corresponding to the input voltage).

Output frequency

0 to 300Hz

Starting torque

0Hz/200%(VC and SVC), 0.8Hz/150%(V/F)

Carrier Frequency

1kHz to 10kHz

Overload capacity

Light overload condition: 150 of the output current, allowing 1 minute of overload every 5 minutes;