Project
|
Description
|
|
Input
|
Input voltage
|
Three-phase 380V ~ 480V
|
|
Rated frequency
|
50/60Hz
|
|
Allowable voltage fluctuation
|
-15% to + 10%
|
|
Allowable frequency fluctuation
|
The allowable range of frequency variation is fLN ± 2% (± 4% for independent power supply network).
Frequency change rate: ≤ 2% fLN/s.
|
|
Output
|
Output voltage range
|
0 ~ input voltage, the error is less than 5%
|
|
Asymmetry of the output voltage
|
Under normal use conditions, in the entire output frequency adjustment range, the asymmetry of the output three-phase voltage should not exceed 1% under the condition of symmetrical load of each phase.
|
|
Output frequency range
|
0 to 300Hz
|
|
Control
characteristics
|
Operation instruction mode
|
Panel control, terminal control, communication control.
|
|
Carrier Frequency
|
1kHz ~ 10kHz, adjustable according to temperature and load characteristics.
|
|
Frequency resolution
|
Digital setting: 0.01Hz, analog setting: maximum frequency x0.1%
|
|
Control mode
|
Closed-loop vector control (VC), open-loop vector control (SVC), V/F control.
|
|
V/F control
|
Linear type, multi-point type, square type.
|
|
Torque control
|
There is PG torque control, no PG torque control.
|
|
Maximum speed
|
300Hz, depending on the electrical and mechanical characteristics of the motor.
|
|
Starting torque
|
0Hz/200%(VC and SVC), 0.8Hz/150%(V/F)
|
|
Torque response
|
<5ms(SVC), <5ms(VC)
|
|
Torque control accuracy
|
± 5%(SVC), ± 3%(VC)
|
|
Speed range
|
1:500(SVC),1:1000(VC)
|
|
Speed accuracy
|
± 0.02% rated speed (VC), ± 0.2% rated speed (SVC), ± 0.5% rated speed (V/F).
|
|
Overload capacity
|
Light overload capacity: 150% of the rated output current, allowing 1 minute of overload every 5 minutes;
The heavy overload capacity is: 180 of the rated output current, and the overload is allowed for 1 minute every 5 minutes.
|
|
Torque compensation
|
Automatic torque compensation function.
|
|
Acceleration and deceleration mode
|
Line, user-defined multi-point curve.
|
|
Automatic voltage adjustment
|
When the grid fluctuates, it can automatically keep the output voltage constant.
|
|
DC braking mode
|
DC braking at startup and DC braking at shutdown.
|
|
Built-in process PID
|
It is convenient to realize the closed-loop control system of process quantity (pressure, temperature, flow, etc.).
|
|
Bus Option
|
CANopen, Modbus RTU, Profibus DP, Profinet
|
|
Special features
|
Free function modules for user-programmable applications: logic function modules, mathematical function modules, timer modules, PID modules, etc.
|
|
Motion control: multi-curve acceleration/deceleration function, timer-controlled run/stop control, etc.
|
|
Crane function: power optimization, crane opening brake function.
|
|
Synchronous control: master/slave synchronous control, speed/torque control.
|
|
Input/output
terminals
|
Input terminal
|
Digital input 5, analog input 2 (voltage 0 ~ +10V or current 0mA/4mA ~ 20mA) standard in the terminal board.
|
|
Output terminal
|
3 channels of digital output (1 channel of collector output and 2 channels of relay output) and 2 channels of analog output (voltage 0 ~ +10V or current 0mA/4mA ~ 20mA) are standard on the terminal board.
|