Product Parameters

No.

Project

Unit

B15-8.83/0.981

B30-8.83/0.981

B50-8.83/0.981

General

Efficient

Fifth generation products

General

Efficient

Fifth generation products

Efficient

Fifth generation products

1

Inlet steam pressure

Mpa

8.83

2

Inlet steam temperature

535

3

Steam intake

t/h

130

119.85

110.4

236

225

211.3

371.5

348.75

4

Exhaust pressure

Mpa

0.981

5

Exhaust temperature

281

269

250.3

268

263

243.3

263

242.4

6

Steam consumption

Kg/kwh

8.67

7.99

7.36

7.87

7.5

7.043

7.43

6.975

7

Power

KW

15000

15000

15000

30000

30000

30000

50000

50000

8

Internal efficiency

%

76.2

80.2

87.1

80.7

82.2

89.6

82.5

90.3

9

Difference value of steam consumption

%

+17.8

+8.56

+11.74

+6.49

+6.52