252kV GIS Combined Switchgear

Negotiable
China
No. 50 Boyang Road, Eastern New District, Taishan District, Tai'an City, Shandong Province
+860538-8639516
+8615615788177
Online Contact
Favorite

Product Introduction

The ZF34-252 GIS produced by the company features a rated current of 5000A and a rated short-circuit breaking current of 63kA. The product is a newly designed integrated, modular, standardized, and compact GIS, occupying less floor space. The circuit breaker employs a self-energy arc-extinguishing principle, offering a simple and reliable structure, strong breaking capacity, and long electrical life. The horizontal circuit breaker is compatible with spring or hydraulic disc spring operating mechanisms, ensuring high reliability and low maintenance requirements. The aluminum alloy enclosure features low temperature rise, corrosion resistance, low eddy current losses, and lighter product weight. The entire bay is transported as a complete unit, significantly reducing on-site construction time. The wiring configurations are flexible, and the product demonstrates strong environmental adaptability, suitable for both indoor and outdoor installation. It is applicable in regions with harsh environmental conditions, high-altitude and earthquake-prone areas, as well as congested urban areas with limited space and mountainous hydropower stations where earthwork excavation is difficult. It is widely applicable to three-phase AC 50Hz power systems with a rated voltage of 252kV, enabling fast, effective, and safe transmission and distribution of electrical energy, including connection, distribution, switching, and dispatching.

Product Parameters

No.

Item

Unit

Parameter

1

Rated voltage

kV

126

252

363

550

2

Rated frequency

Hz

50

3

Rated current

A

3150

4000/5000

5000

5000/6300

4

Rated short-circuit breaking current

kA

40

50

63

63

5

Rated short-time withstand current

kA

40

50

63

63

6

Rated short-circuit duration

s

4

3

3

3

7

Rated peak withstand current

kA

100

125

171

171

8

Rated short-duration power-frequency withstand voltage (1min, RMS)

Phase-to-phase, phase-to-ground

kV

230

460

510

740

Across open contact

kV

230+73

460+146

510+210

740+318

9

Rated lightning impulse withstand voltage

Phase-to-phase, phase-to-ground

kV

550

1050

1175

1675

Across open contact

kV

550+103

1050+206

1175+295

1675+450

10

Rated switching impulse withstand voltage

Phase-to-ground

kV

/

/

950

1300

Phase-to-phase

kV

/

/

1425

/

Across open contact

kV

/

/

950+295

1175+450

11

Partial discharge

Test voltage

kV

151

175

436

381

Bay

pC

≤3

≤3

≤3

≤3

Insulating parts

pC

≤3

≤3

≤3

≤3

12

SF6 gas pressure

Circuit breaker

Rated

MPa

0.6

0.6

0.6

0.6

Alarm

MPa

0.55

0.55

0.55

0.55

Lockout

MPa

0.5

0.5

0.5

0.5

Others

Rated

MPa

0.4

0.4

0.4

0.4

Minimum functional

MPa

0.35

0.35

0.30

0.30

13

Mechanical endurance

Circuit breaker

Operations

10000

10000

10000

10000

Disconnector

Operations

10000

10000

10000

10000

High-speed and maintenance earthing switch

Operations

10000

10000

10000

10000

14

SF6 gas annual leakage rate

%

≤0.05

≤0.1

≤0.03

≤0.03