Product Parameters

No.

Item

Unit

Parameter

1

Rated voltage

kV

126

252

363

550

2

Rated frequency

Hz

50

3

Rated current

A

3150

4000/5000

5000

5000/6300

4

Rated short-circuit breaking current

kA

40

50

63

63

5

Rated short-time withstand current

kA

40

50

63

63

6

Rated short-circuit duration

s

4

3

3

3

7

Rated peak withstand current

kA

100

125

171

171

8

Rated short-duration power-frequency withstand voltage (1 min, RMS)

Between phases, phase-to-earth

kV

230

460

510

740

Across the isolating distance

kV

230+73

460+146

510+210

740+318

9

Rated lightning impulse withstand voltage

Between phases, phase-to-earth

kV

550

1050

1175

1675

Across the isolating distance

kV

550+103

1050+206

1175+295

1675+450

10

Rated switching impulse withstand voltage

Phase-to-earth

kV

/

/

950

1300

Between phases

kV

/

/

1425

/

Across the isolating distance

kV

/

/

950+295

1175+450

11

Partial discharge

Test voltage

kV

151

175

436

381

Bay

pC

≤3

≤3

≤3

≤3

Insulating parts

pC

≤3

≤3

≤3

≤3

12

SF6 gas pressure

Circuit breaker

Rated

MPa

0.6

0.6

0.6

0.6

Alarm

MPa

0.55

0.55

0.55

0.55

Blocking

MPa

0.5

0.5

0.5

0.5

Others

Rated

MPa

0.4

0.4

0.4

0.4

Minimum functional

MPa

0.35

0.35

0.30

0.30

13

Mechanical endurance

Circuit breaker

Operations

10000

10000

10000

10000

Disconnector

Operations

10000

10000

10000

10000

High-speed and maintenance earthing switch

Operations

10000

10000

10000

10000

14

SF6 gas annual leakage rate

%

≤0.05

≤0.1

≤0.03

≤0.03