The ZF39-126 GIS manufactured by the company features a rated current of 3150A, with the main busbar capable of reaching 4000A, and a rated short-time withstand current and duration of 40kA/4S. The product is a newly designed integrated, modularized, standardized, and compact GIS, occupying less floor space. The circuit breaker equipped in the GIS adopts the self-energy arc-extinguishing principle of "thermal expansion + assisted blowing," featuring a simple and reliable structure, strong breaking capacity, a total breaking time of three cycles, and a long electrical life. The circuit breaker is fitted with the CTB-Ⅰ spring operating mechanism, which is simple and compact in structure, highly reliable, requires minimal maintenance, and has a mechanical life of up to 10,000 operations, meeting the "oil-free" requirement. The metal aluminum alloy enclosure offers low temperature rise, corrosion resistance, low eddy current losses, and lighter product weight. The entire bay is transported as a single unit, significantly shortening the on-site construction period. The wiring configurations are flexible, and the product exhibits strong environmental adaptability, suitable for both indoor and outdoor installation. It is applicable to areas with harsh environmental conditions, high-altitude and earthquake-prone regions, as well as congested urban areas with limited space and mountainous hydropower stations where earthwork excavation is difficult. It is suitable for three-phase AC 50Hz power systems with a rated voltage of 72.5 to 126kV, enabling fast, effective, and safe power transmission and distribution network connections, distribution, switching, and dispatching.
126kV GIS Switchgear Assembly
Product Introduction
Product Parameters
|
No. |
Item |
Unit |
Parameter |
|||||
|
1 |
Rated voltage |
kV |
126 |
252 |
363 |
550 |
||
|
2 |
Rated frequency |
Hz |
50 |
|||||
|
3 |
Rated current |
A |
3150 |
4000/5000 |
5000 |
5000/6300 |
||
|
4 |
Rated short-circuit breaking current |
kA |
40 |
50 |
63 |
63 |
||
|
5 |
Rated short-time withstand current |
kA |
40 |
50 |
63 |
63 |
||
|
6 |
Rated short-circuit duration |
s |
4 |
3 |
3 |
3 |
||
|
7 |
Rated peak withstand current |
kA |
100 |
125 |
171 |
171 |
||
|
8 |
Rated short-duration power-frequency withstand voltage (1min, RMS) |
Phase-to-phase, phase-to-ground |
kV |
230 |
460 |
510 |
740 |
|
|
Across open contact |
kV |
230+73 |
460+146 |
510+210 |
740+318 |
|||
|
9 |
Rated lightning impulse withstand voltage |
Phase-to-phase, phase-to-ground |
kV |
550 |
1050 |
1175 |
1675 |
|
|
Across open contact |
kV |
550+103 |
1050+206 |
1175+295 |
1675+450 |
|||
|
10 |
Rated switching impulse withstand voltage |
Phase-to-ground |
kV |
/ |
/ |
950 |
1300 |
|
|
Phase-to-phase |
kV |
/ |
/ |
1425 |
/ |
|||
|
Across open contact |
kV |
/ |
/ |
950+295 |
1175+450 |
|||
|
11 |
Partial discharge |
Test voltage |
kV |
151 |
175 |
436 |
381 |
|
|
Bay |
pC |
≤3 |
≤3 |
≤3 |
≤3 |
|||
|
Insulating parts |
pC |
≤3 |
≤3 |
≤3 |
≤3 |
|||
|
12 |
SF6 gas pressure |
Circuit breaker |
Rated |
MPa |
0.6 |
0.6 |
0.6 |
0.6 |
|
Alarm |
MPa |
0.55 |
0.55 |
0.55 |
0.55 |
|||
|
Blocking |
MPa |
0.5 |
0.5 |
0.5 |
0.5 |
|||
|
Others |
Rated |
MPa |
0.4 |
0.4 |
0.4 |
0.4 |
||
|
Minimum functional |
MPa |
0.35 |
0.35 |
0.30 |
0.30 |
|||
|
13 |
Mechanical life |
Circuit breaker |
Operations |
10000 |
10000 |
10000 |
10000 |
|
|
Disconnector |
Operations |
10000 |
10000 |
10000 |
10000 |
|||
|
High-speed and maintenance earthing switch |
Operations |
10000 |
10000 |
10000 |
10000 |
|||
|
14 |
SF6 gas annual leakage rate |
% |
≤0.05 |
≤0.1 |
≤0.03 |
≤0.03 |
||
Related Products
On Extreme-NEE Series Circuit Breaker
Advanced Surface Defect Detection System
GGD AC Low-voltage Distribution Cabinet
Electric Energy Metering Box
Automated Chassis
EPS Emergency Power Supply
Mineral-insulated Compact Busway (Fire-resistant Busduct)
Overhead Cable Quick Tap Connector
10kV Reactor
BKM3HU Molded Case Circuit Breaker
Dry-Type Vacuum On-Load Tap-Changer