The DWK-type pole-mounted automatic reactive power compensation device is primarily used for 6-10kV transmission lines. It can automatically control the connection and disconnection of parallel capacitors based on parameters such as voltage, time, power factor, and reactive power through an automatic controller. This helps improve the line’s power factor, reduce line losses, and enhance voltage quality.
DWK-type Pole-mounted Automatic Reactive Power Compensation Device
|
Altitude |
The altitude is not higher than 2000m (special requirements must be specified when ordering) |
|
Ambient temperature |
-25 ℃ ~ +45 ℃ (special requirements must be specified when ordering) |
|
Ambient humidity |
<90% at 25 ℃ |
|
Anti-fouling grade |
Level III |
|
Rated frequency |
50Hz |
|
Measurement accuracy |
0.5 level |
|
Installation Environment |
No severe mechanical vibration affecting the insulation performance of the device, no harmful gases and vapors, no conductive or explosive dust |
|
Voltage level |
6kV or 10kV |
|
Control mode |
Voltage reactive power control, power factor control, voltage control, time control, voltage time control |
|
Protection function |
With over-voltage, under-voltage, time-limited quick-break, over-current, unbalanced current (including phase loss) protection |
|
Display function |
Real-time display of line voltage, current, power factor, reactive power, capacitor switching, etc. |
|
Recording function |
Can record the whole point data, action data, fault data, etc. |
|
Communication mode |
With standard RS485 communication interface, GPRS remote monitoring and wireless monitoring can be realized |
|
Capacitor discharge time |
A discharge resistor is installed inside the capacitor. After the capacitor is disconnected from the power supply, it can drop below 75 volts from the peak value of the rated voltage within 10 minutes. |
|
Voltage transformer |
6/0.22kV or 10/0.22kV |
|
Reactor reactance rate |
The appropriate reactance rate can be selected according to the actual situation, such as: 1%, 5%, 6%, 12%, etc. |
|
Vacuum contactor life |
100000 times |