The KYN28 type armored withdrawable indoor AC metal-enclosed switchgear (hereinafter referred to as the switchgear) is a three-phase AC 50Hz indoor complete distribution device used for receiving and distributing 3-12kV network electrical energy, as well as controlling, protecting, and monitoring circuits. This product allows various types of microcomputer-based integrated relay protection devices to be installed on the relay panel, enabling intelligent control of the system. It features remote control, remote measurement, remote signaling, and remote adjustment functions, and controls the on-site network through a CAN bus with a communication interface. The switchgear includes protection functions to prevent incorrect breaker operation, prevent pulling or pushing the truck with load, prevent closing the grounding switch while under load, prevent power supply through the grounding switch in the grounded position, and prevent accidental entry into live compartments—collectively known as the "Five Prevention" functions. The cabinet can be equipped with VSI (i.e., ZN63) or ZN12V vacuum circuit breakers, as well as imported VD4 vacuum circuit breakers and VC series vacuum contactors.
KYN28 type high-voltage switchgear
Product Introduction
Product Parameters
|
Name |
Unit |
Data |
|
|
Rated voltage |
kV |
12 |
|
|
Rated insulation level |
1min power frequency withstand voltage (interphase, ground/fracture) |
kV |
42/48 |
|
Lightning impact withstand voltage (phase-to-phase, ground/fracture) |
kV |
75/85 |
|
|
Rated frequency |
Hz |
50 |
|
|
Rated current |
A |
630~3150 |
|
|
Rated current of main bus |
A |
1250, 1600, 2000, 2500, 3150 |
|
|
Rated current of branch bus |
A |
630, 1250, 1600, 2000, 2500, 3150 |
|
|
Rated short-time withstand current (4S) |
kA |
16, 20, 25, 31.5, 40, 50 |
|
|
Rated peak withstand current (※ ※) |
kA |
40, 50, 63, 80, 100, 125 |
|
|
Protection level |
- |
Enclosure IP4X, breaker chamber door open to IP2X |
|
|
Overall dimensions (width * depth * height) |
mm |
800(1000)* 1300(1500)* 2200(※ ※ ※) |
|
|
Weight |
Kg |
800~1200 |
|
※: The rated current of the branch bus can reach 3150A in air cooling
※ ※: The current transformer according to the capacity should be considered separately
※ ※ ※: The rated short-term withstand current is 31.5kA and below, and the cabinet width is 800mm when the rated current of branch bus is 1250A and below; The rated short-term withstand current is 40kA and above, the cabinet width is 1000mm when the rated current of branch bus is 1250A or above, and the cabinet depth is determined according to the project conditions.
Other products from this supplier

SVR Line Automatic Voltage Regulator

DWK-type Pole-mounted Automatic Reactive Power Compensation Device

Skid-mounted substation

10kV Distribution Network Series Compensation Device

TBB-type high-voltage automatic reactive power compensation device

IPSVR Intelligent Line Voltage Regulator

Box-type substation

HSVG High-Voltage Static Var Generator

GGD type low-voltage switchgear

S22(20) series oil-immersed distribution transformer

Landscape media box-type transformer

GCS type low-voltage withdrawable switchgear
Related Products
NISELA Series Environmentally Friendly Gas-Insulated Ring Main Unit
220kV level capacity: 31500kV·A~240000kV.A three-phase double winding on-load voltage regulating power transformer
72.5kV 1250A 31.5kA SF6 free Gas-insulated Metal-enclosed Switchgear
KYN28i-12 intelligent indoor high-voltage alternating current metal-enclosed armored switchgear
Epoxy resin vacuum casting dry-type transformer
All-Black Solar Panel - 54X 410-430W
Amorphous Alloy Dry Type Transformer
SCB13 Epoxy Resin Cast Dry-Type Power Transformer
10kV, 20kV, 35kV series resin cast dry-type power transformer
ZH3C-72.5 Environmentally Friendly Gas-Insulated Metal-Enclosed Switchgear 72.5kV, 3150A, 40kA
Vacuum Interrupter