Usage characteristics:
①Long-term allowable working temperature of the cable: PVC insulation is 70°C; polyethylene insulation is 70°C; cross-linked polyethylene insulation is 90°C.
②Short-term maximum working temperature of the cable: during a short circuit (5s); PVC insulation is 160°C; polyethylene insulation is 130°C; cross-linked polyethylene insulation is 250°C.
③The cable installation temperature should not be lower than -20°C.
④The cable operating ambient temperature is -40°C ~ 40°C, with relative humidity not less than 90% during the rainy season.
⑤Allowable bending radius of the cable:
For cables with a rated voltage of 0.6/1kV and below:
If the cable outer diameter D < 25mm, the bending radius should be no less than 4D.
If the cable outer diameter D ≥ 25mm, the bending radius should be no less than 6D.
For cables with a rated voltage of 10kV:
For single-core cables, the bending radius should be no less than 20(D+d)mm.
For multi-core cables, the bending radius should be no less than 15(D+d)mm.
Among them:
D - the actual outer diameter of the cable in mm;
d - the actual outer diameter of the cable conductor in mm.