1. Executive Standards

  • GB/T 5023.1-2008 Polyvinyl chloride insulated cables of rated voltages up to and including 450/750V - Part 1: General requirements

  • GB/T 5023.3-2008 Polyvinyl chloride insulated cables of rated voltages up to and including 450/750V - Part 3: Non-sheathed cables for fixed wiring

  • JB/T 8734-2012 Polyvinyl chloride insulated cables and wires and flexible cords of rated voltages up to and including 450/750V

  • GB/T 3956-2008 Conductors of insulated cables (Class 1 solid conductors)

  • GB/T 19666-2019 General rules for flame-retardant and fire-resistant wires and cables (basis for flame-retardant class determination)

  • GB/T 18380.3-2008 Tests on electric and optical fibre cables under fire conditions

  • GB 50016-2014 Code for fire protection design of buildings (basis for type selection and adaptation)

The product must pass CCC mandatory certification, with the model, flame-retardant class, rated voltage, executive standard, and manufacturer name clearly printed on the cable body.


2. Product Structure

ZR-BV features a two-layer structure (conductor + insulation layer) with no outer sheath:

🔹 Conductor

  • Material: High-purity oxygen-free copper (TU1/TU2), copper purity ≥99.95%, conductivity ≥98% IACS

  • Construction: Class 1 solid conductor (single strand) or Class 2 stranded conductor (a few thicker round copper wires)

  • Appearance: Purplish-red metallic luster; after stripping the insulation, the conductor should be bright and new-looking, with no blackening, roughness, or powdery oxides—this is the most direct criterion for judging whether the copper material is qualified

🔹 Insulation Layer

  • Material: Flame-retardant polyvinyl chloride (ZR-PVC), with halogen-based flame retardants (such as chlorinated paraffin + antimony trioxide) or inorganic flame retardants added to the PVC base resin

  • Flame-retardant mechanism: Upon exposure to fire, the flame retardant releases hydrogen halide to dilute oxygen, absorbs heat through decomposition to lower temperature, and forms a dense carbonized layer on the surface to block heat; self-extinguishes within 10 seconds after the fire source is removed

  • Characteristics: Insulation resistance ≥0.010 MΩ·km (70℃), resistant to acids and alkalis, oil-resistant, moisture-proof, and mold-resistant

Product Parameters

Item

Parameter

Rated voltage U₀/U

450/750V

Maximum conductor operating temperature

70℃ (determined by PVC insulation characteristics)

Short-circuit temperature (within 5s)

≤ 160℃

Ambient temperature during installation

0℃ (installation below this temperature may cause insulation embrittlement)

Bending radius

≥4D when outer diameter D<25mm; ≥6D when D≥25mm

Power-frequency withstand voltage test

2500V / 1min without breakdown

Flame-retardant class

Four classes: ZA / ZB / ZC / ZD (GB/T 19666-2019)

Coil length

100m/coil, tolerance ≤±0.5%